Does anyone have ¢ picture that can go in this report for the following location?
Outlet: Sink Faucet (02CF034)
Location: Classroom 208, southwest wall
Results: P1=19 parts per billion, P2=12 parts per billion,
F1=3 parts per billion, F2=2 parts per billion
These results suggest the highest contribution of lead may be from the faucet and its
connecting plumbing. The base of this faucet is chrome plated brass, and has a brass
connection on the underside of the sink. Connecting plumbing in the Image cabinet under
the sink should be checked for brass components and copper piping Available with lead solder.
No
Replacement of this faucet and its connection plumbing with lead-free materials will
significantly reduce lead exposure at this location. If replacement is not currently feasible, sample results
indicate that flushing this tap for 3 minutes following periods of stagnation is likely to reduce lead
concentrations and lead exposure.